Input Power 12 (15 for 0-10V) to 30VDC/24VAC 15mA max. HS Element Digitally profiled thin-film capacitive non removable Accuracy at 25°C from 10-90% RH ±3% Reset Rate* 24 hours Stability ±1% @ 20°C (68°F) annually for two years Operating Humidity Range 0 to 100% RH (non-condensing) Temperature Effect (0.0015%RH(T°C-25))+(%RH0.0008abs(T°C - 25)) Analog Output 0-5V 3-wire observe polarity Scaling 0–100% RH Operating Temperature Range -40° to 50°C (-40° to 122°F) 1-year limited warranty*Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.One side of transformer secondary is connected to signal common. Isolation transformer or dedicated power supply may be required